AIR CONDITIONING – AIR CONDITIONING SYSTEM (for Automatic Air Conditioning Sys-
tem)AC–19
AC
HINT:
*1: It differs depending on the user setting.
2. ACTIVE TEST
HINT:
Using the intelligent tester to perform Active Tests allows
relays, VSVs, actuators and other items to be operated
without removing any parts. This non-intrusive functional
inspection can be very useful because intermittent
operation may be discovered before parts or wiring is
disturbed. Performing Active Tests early in
troubleshooting is one way to save diagnostic time. Data
List information can be displayed while performing Active
Tests.
(a) Connect the intelligent tester to the DLC3.
A/I DAMP TARGAir inlet damper target position /
min.: -14%, max.: 113.5%Changes depending on air inlet
damper position-
A/O DAMP TARGAir outlet damper target position /
min.: -14%, max.: 113.5%Changes depending on air outlet
damper position-
BLOWER LEVELBlower motor speed level / min.:
Level 0, max.: Level 31Changes depending on blower
level-
REAR ROOM TEMPRoom temperature sensor (Rear)
/ min.: -6.5
C (20.3F), max.:
57.25C (135.05F)Actual cabin temperature (Rear) -
R-EVAP TEMP SENRr. EVAP temperature sensor
(Rear) / min.: -29.7
C (-21.46F),
max.: 59.55
C (139.19F)Actual evaporator temperature
(Rear)-
SET TEMP REARSet temperature (Rear) / min.: 0,
max. 255Actual set temperature -
ESTIMATE TEMP-REstimated temperature (Rear) /
min.: -358.4
C (-613.12F), max.:
358.4
C (677.12F)--
A/M DAMP POS-RAir mix damper position (Rear) /
min.: -14%, max.: 113.5%Changes depending on the set
temperature (Rear)-
A/O DAMP POS-RAir outlet mode damper position
(Rear) / min.: -14%, max.: 113.5%Changes depending on air outlet
damper position (Rear)-
A/M DAMP TARG-RAir mix damper target position
(Rear) / min.: -14%, max.: 113.5%Changes depending on the set
temperature (Rear)-
A/O DAMP TARG-RAir outlet damper target position
(Rear) / min.: -14%, max.: 113.5%Changes depending on air outlet
damper position (Rear)-
BLOWER LEVEL-RBlower motor speed level (Rear) /
min.: Level 0, max: Level 31Changes depending on blower
level (Rear)-
SET TEMP SHIFT Shift set temperatureChanges depending on shift set
temperature *1-
AIR INLET MODE Air inlet modeChanges depending on air inlet
mode *1-
COMPRESSOR MODE Compressor modeChanges depending on
compressor mode *1-
COMPRS/DEF MODE Compressor/DEF operation modeChanges depending on
compressor/DEF operation mode
*1-
FOOT/DEF OPER Foot/DEF auto modeChanges depending on Foot/DEF
auto mode *1-
AUTO BLOW UPFoot/DEF automatic blow up
functionChanges depending on Foot/DEF
automatic blow up function *1-
#CODESNumber of Trouble Codes / min.:
0, max.: 255-- Tester Display Measurement Item/Range Normal Condition Diagnostic Note
AIR CONDITIONING – AIR CONDITIONING SYSTEM (for Automatic Air Conditioning Sys-
tem)AC–25
AC
(b) As each damper, motor and relay automatically
operate actuator check at 1-second intervals from
step No. 1 to No. 10 continuously, check the
temperature and air flow visually and by hand.
If the slower display is desired, press the DEF
switch and change it to step operation. Each time
the DEF switch is pressed, the display changes by 1
step.
HINT:
• Codes are displayed from smaller to larger
numbers in order.
• To cancel the check mode, press the OFF switch.
Step No.Display
codeConditions
Fr. Blower
levelFr. Air flow
ventAir inlet
damperMagnetic
clutchFr. Driver,
passenger
side air
mix
damperRr. Blower
levelRr. Air flow
ventRr. Air mix
damper
1 0 0 FACE FRESH OFF"COOL"
side
(Full
closed)0 FACE1"COOL"
side
(Full
closed)
2 1 1 FACE FRESH OFF"COOL"
side
(Full
closed)1 FACE1"COOL"
side
(Full
closed)
3 2 16 FACE FRESH ON"COOL"
side
(Full
closed)10 FACE1"COOL" /
"HOT"
(40% open)
4316FACEFRESH /
RECIRCUL
AT I O NON"COOL"
side
(Full
closed)10 FACE2"COOL" /
"HOT"
(40% open)
5416FACERECIRCUL
AT I O NON"COOL" /
"HOT"
(50% open)10 B/L"COOL" /
"HOT"
(40% open)
6516B/LRECIRCUL
AT I O NON"COOL" /
"HOT"
(50% open)10 B/L"COOL" /
"HOT"
(60% open)
7616FOOTRECIRCUL
AT I O NON"HOT" side
(Full open)10 B/L"COOL" /
"HOT"
(60% open)
8716FOOTRECIRCUL
AT I O NON
"HOT" side
(Full open)10 FOOT"COOL" /
"HOT"
(60% open)
9816FOOT /
DEF.RECIRCUL
AT I O NON"HOT" side
(Full open)10 FOOT"COOL" /
"HOT"
(86.5%
open)
10931DEF.RECIRCUL
AT I O NON"HOT" side
(Full open)31 FOOT"COOL" /
"HOT"
(86.5%
open)