Page 3555 of 4323
BE2D6±02
I10154
I24870
12
6
± BODY ELECTRICALENGINE IMMOBILISER SYSTEM
BE±143
3547 Author: Date:
2005 SEQUOIA (RM1146U)
INSPECTION
1. INSPECTION TRANSPONDER KEY COIL CONTINU-
ITY
Check that there is continuity between terminals 1 and 2.
If continuity is not as specified, replace the coil.
2. INSPECT TRANSPONDER KEY ECU CIRCUIT
Connect the wire harness side connector to the ECU and in-
spect the wire harness side connector from the back side, as
shown in the table below.
ConditionTester connectionSpecified condition
Always6 ± 12Battery positive voltage
If the circuit is as specified, replace the ECU with a new one.
If the circuit is not as specified, inspect the circuit connected to
other parts.
Page 3638 of 4323
BO0139
Rear End
Front EndBO46O±01
± BODYSLIDING ROOF
BO±77
3630 Author: Date:
2005 SEQUOIA (RM1146U)
SLIDING ROOF
ON±VEHICLE INSPECTION
INSPECT SLIDING ROOF GLASS ALIGNMENT
(a) Start the engine and check the operation time of the slid-
ing roof.
Operation time:
Approx. 6 secs.
(b) Check for abnormal noise or binding during operation.
(c) With the sliding roof fully closed, check for water leakage.
(d) Check for a difference in level between the sliding roof
weatherstrip and roof panel.
Front end:
0 - 2.0 mm (0 ± 0.079 in.)
0 + 1.0 mm (0 + 0.039 in.)
Side end:
0 ± 1.5 mm (0 ± 0.059 in.)
Rear end:
0 ± 1.0 mm (0 ± 0.039 in.)
0 + 2.0 mm (0 + 0.079 in.)
Page 3738 of 4323

I21357
Sight Glass
AC1JT±06
± AIR CONDITIONINGAIR CONDITIONING SYSTEM
AC±3
3730 Author: Date:
2005 SEQUOIA (RM1146U)
ON±VEHICLE INSPECTION
1. INSPECT REFRIGERANT VOLUME
Observe the sight glass on the liquid tube.
Test conditions:
Running engine at 1,500 rpm
Single A/C:
Front blower speed control dial at ºHIº position
Dual A/C:
Front and rear blower speed set at ºHIº position
A/C switch ON
Single A/C:
Front temperature control dial at ºMAX. COOLº position
Dual A/C:
Front temperature control dial at ºMAX. COOLº position
Rear temperature control set at 18.5°C (65°F)
Fully open the doors
ItemSymptomAmount of refrigerantRemedy
1Bubbles are present in sight glass continu-
ouslyInsufficient*
(1) Check for gas leakage with gas leak de-
tector and repair if necessary
(2) Add refrigerant until bubbles disappear
2No bubbles are present in sight glassNone, sufficient or too muchRefer to items 3 and 4
3No temperature difference between com-
pressor inlet and outletEmpty or nearly empty
(1) Check for gas leakage with gas leak de-
tector and repair if necessary
(2) Add refrigerant until bubbles disappear
4Temperature between compressor inlet and
outlet is noticeably differentCorrect or too muchRefer to items 5 and 6
5Immediately after air conditioning is turned
off, refrigerant in sight glass stays clearToo much
(1) Discharge refrigerant
(2) Evacuate air and charge proper amount
of purified refrigerant
6When air conditioning is turned off, refriger-
ant foams and then stays clearCorrect±
*: Bubbles in the sight glass with ambient temperature higher than usual can be considered normal if cooling
is sufficient.
Page 3739 of 4323
I21803
Single A/C:
Dual A/C: AC±4
± AIR CONDITIONINGAIR CONDITIONING SYSTEM
3731 Author: Date:
2005 SEQUOIA (RM1146U)
2. INSPECT REFRIGERANT PRESSURE WITH MAN-
IFOLD GAUGE SET
This is a method for checking the A/C system by using a man-
ifold gauge set. Read the manifold gauge pressure when the
conditions below are met.
Test conditions:
Temperature at the air inlet with R/F switch set at RECIRC
is 30 to 35°C (86 to 95°F)
Engine running at 1500 rpm
Blower speed control switch at ºHIº position
Temperature control dial at ºMAX. COOLº position
Dual A/C:
Rear temperature control set at 18.5°C (65°F)
HINT:
Gauge indications may vary slightly due to ambient tempera-
ture conditions.
(1) Normally functioning refrigeration system.
Gauge reading:
Single A/C:
GaugeMPakgf´cm2
Low pressure0.15 to 0.251.5 to 2.5
High pressure1.6 to 1.816 to 18
Dual A/C:
GaugeMPakgf´cm2
Low pressure0.25 to 0.352.5 to 3.5
High pressure1.9 to 2.119 to 21
Page 3742 of 4323

I22614
Condition: Insufficient cooling
Single A/C:
Dual A/C:
I22614
Condition: Insufficient cooling
Single A/C:
Dual A/C:
NOTE: These indications
are shown when the refrig-
eration system has been
opened and the refrigerant
has been charged without
vacuum purging.
± AIR CONDITIONINGAIR CONDITIONING SYSTEM
AC±7
3734 Author: Date:
2005 SEQUOIA (RM1146U)
(6) Refrigerant overcharged or insufficient cooling of
condenser
Symptom seen in
refrigeration systemProbable causeDiagnosisRemedy
Pressure too high on both low
and high pressure sides
No air bubbles seen through the
sight glass even when the engine
rpm is lowered Unable to develop sufficient per-
formance due to excessive refrig-
erant
Insufficient cooling of condenser Excessive refrigerant in
cycle"refrigerant overcharged
Condenser cooling
insufficient"condenser fins
clogged or cooling fan faulty
(1) Clean condenser
(2) Check cooling fan with fluid
coupling operation
(3) If (1) and (2) are in normal
state, check amount of refrigerant
and charge proper amount of re-
frigerant
(7) Air present in refrigeration system
Symptom seen in
refrigeration systemProbable causeDiagnosisRemedy
Pressure too high on both low
and high pressure sides
The low pressure piping hot to
the touch
Bubbles seen in sight glass
Air in refrigeration system
Air present in refrigeration sys-
tem
Insufficient vacuum purging
(1) Check compressor oil to see if
it is dirty or insufficient
(2) Evacuate air and charge new
refrigerant
Page 3744 of 4323

± AIR CONDITIONINGAIR CONDITIONING SYSTEM
AC±9
3736 Author: Date:
2005 SEQUOIA (RM1146U)
3. INSPECT IDLE±UP SPEED
(a) Warm up the engine.
(b) Inspect idle±up speed when the following conditions are
established.
Warm up engine
Blower speed control switch at ºHIº position
A/C switch ON
Temperature control dial at ºCOOLº position
Magnetic clutch conditionIdle±up speed
Magnetic clutch not engaged700 ± 50 rpm
Magnetic clutch engaged780 ± 50 rpm
If idle speed is not as specified, check the Idle control system.
4. INSPECT FOR LEAKAGE OF REFRIGERANT
(a) Perform under the following conditions:
Stop the engine.
Secure good ventilation (If not, the gas leak detec-
tor may react to volatile gases witch are not refriger-
ant, such as evaporated gasoline and exhaust gas.)
Repeat the test 2 or 3 times.
Make sure that there is some refrigerant remaining
in the refrigeration system.
When the compressor is OFF: approx. 392 to 588
kPa (4 to 6 kgf/ cm
2, 57 to 85 psi)
(b) Bring the gas leak detector close to the drain hose before
performing the test.
HINT:
After the blower motor stopped, leave the cooling unit for
more than 15 minutes.
Bring the gas leak detector sensor under the drain hose.
When bringing the gas leak detector close to the drain
hose, make sure that the gas leak detector does not react
to the volatile gases.
If such reaction is unavoidable, the vehicle must be lifted up.
(c) If gas leak is not detected on the drain hose, remove the
blower motor linear controller from the cooling unit. Then
insert the gas leak detector sensor into the unit and per-
form the test.
(d) Disconnect the connector and leave the pressure switch
for approx. 20 minutes. Then bring the gas leak detector
close to the pressure switch and perform the test.
(e) Bring the gas leak detector close to the refrigerant lines
and perform the test.
Page 3747 of 4323

N13790
Low Pressure
Service Valve
High Pressure
Service Valve
I21358
Properly
Charged
Insufficiently
Charged AC±12
± AIR CONDITIONINGAIR CONDITIONING SYSTEM
3739 Author: Date:
2005 SEQUOIA (RM1146U)
3. CHARGE REFRIGERANT INTO REFRIGERANT SYS-
TEM
If there is no leak after refrigerant leak check, charge the proper
amount of refrigerant into the refrigeration system.
CAUTION:
Never run the engine when charging the system
through the high pressure side.
Do not open the low pressure side valve when the
system is being charged with liquid refrigerant.
(a) Open the high pressure side valve fully.
(b) Charge specified amount of refrigerant, then close the
high pressure side valve.
HINT:
The system is fully charged if bubbles cannot be seen through
the sight glass.
(c) Partially charge the refrigeration system with refrigerant.
(1) Prepare the vehicle:
Running engine at 1,500 rpm
Single A/C:
Front blower speed control dial at ºHIº posi-
tion
Dual A/C:
Front and rear blower speed set at ºHIº posi-
tion
Single A/C:
Front temperature control dial at ºMAX.
COOLº position
Dual A/C:
Front temperature control dial at ºMAX.
COOLº position
Rear temperature control set at 18.5°C
(65°F)
Air inlet control set at ºRECIRCº
Fully open doors (Sliding roof: closed)
(2) Open the low pressure side valve.
CAUTION:
Do not open the high pressure side valve.
(d) Charge refrigerant until bubbles disappear and check the
pressure on the gauge through the sight glass.
Page 3759 of 4323

AC3GV±02
I21372
I21373
AC±24
± AIR CONDITIONINGCOOLING UNIT
3751 Author: Date:
2005 SEQUOIA (RM1146U)
COOLING UNIT
ON±VEHICLE INSPECTION
1. INSPECT FOR LEAKAGE OF REFRIGERANT
(a) Remove the console box assembly.
(b) Remove the glove compartment door.
(c) Remove the lower No. 2 finish panel.
(d) Remove the heater to register duct No. 4.
(e) Remove the lower LH finish panel.
(f) Remove the lower cover (See page BO±89).
(g) Remove the blower controller.
(1) Disconnect the connector.
(2) Remove the 2 screws and blower motor linear con-
troller.
(h) Using a gas leak detector, check for leakage.
If there is leakage, check the tightening torque at the joints or
check the evaporator.
(i) Install the blower motor linear controller with the 2 screws.
(j) Install the lower cover.
(k) Install the lower LH finish panel.
(l) Install the lower No.2 finish panel.
(m) Install the glove compartment door (See page BO±97).
2. INSPECT EXPANSION VALVE
(a) Set the manifold gauge set.
(b) Run the engine.
(c) Check quantity of gas with the sight glass in refrigeration
cycle.
(1) Run the engine at 1,500 rpm for at least 5 minutes.
(2) Then check that the high pressure reading is 1.37
to 1.57 Mpa (14 to 16 kgm/cm
2, 199 to 228 psi).
(d) Check the expansion valve.
If the expansion valve is faulty, the low pressure reading will
drop to 0 kPa (0 kgf/cm
2, 0 psi).
HINT:
When the low pressure reading drops to 0 kPa (0 kgf/cm
2, 0
psi), there is no difference in temperature between the IN and
OUT sides of the receiver.
3. INSPECT THERMISTOR RESISTANCE
(a) Disconnect the connector.
(b) Measure the resistance between terminals.
Standard resistance: 1,500 W at 25°C (77°F)
If resistance is not as specified, replace the thermistor.