Page 377 of 455

82AIR CONDITIONING
2
ADJUSTMENT SERVICING PRECAUTIONS
Care must be taken when handling refrigeration
system components. Units must not be lifted by their
hoses, pipes or capillary lines. Hoses and lines must
not be subjected to any twist or stress. Ensure that
hoses are positioned in their correct run before fully
tightening the couplings, and ensure that all clips and
supports are used. Torque wrenches of the correct
type must be used when tightening refrigerant
connections to the stated value. An additional spanner
must be used to hold the union to prevent twisting of
the pipe.
Before connecting any hose or pipe ensure that
refrigerant oil is applied to the seat of the new '0' ring
but not to the threads.
Check the oil trap for the amount of oil lost.
All protective plugs on components must be left in
place until immediately prior to connection.
The receiver/drier contains desiccant which absorbs
moisture. It must be positively sealed at all times.
CAUTION: Whenever the refrigerant
system is opened, the receiver/drier must
be renewed immediately before evacuating
and recharging the system.
Use alcohol and a clean cloth to clean dirty
connections.
Ensure that all new parts fitted are marked for use
withR134a.
Refrigerant oil
Use the approved refrigerant lubricating oil - Nippon
Denso ND-OIL 8.
CAUTION: Do not use any other type of
refrigerant oil.
Refrigerant oil easily absorbs water and must not be
stored for long periods. Do not pour unused oil back
into the container.
When renewing system components, add the
following quantities of refrigerant oil:
Condenser 40ml..........................................................
Evaporator 80ml..........................................................
Pipe or hose 20ml........................................................
Receiver/drier 20ml......................................................Total quantity of refrigerant oil in system = 140ml
A new compressor is sealed and pressurised with
Nitrogen gas, slowly release the sealing cap, gas
pressure should be heard to release as the seal is
broken.
NOTE: A new compressor should always
have its sealing caps in place and these
must not be removed until immediately
prior to fitting
A new compressor is supplied with an oil fill of 140ml.
A calculated quantity of oil must be drained from a
new compressor before fitting.
To calculate the quantity of oil to be drained:
1.Remove sealing plugs from the OLD
compressor.
2.Invert compressor and gravity drain oil into
measuring cylinder. Rotating the compressor
clutch plate will assist complete draining.
3.Note the quantity of oil drained (Yml).
4.Calculate the quantity (Qml) of oil to be drained
from the NEW compressor using the following
formula:
Xml - (Yml + 20ml) = Qml
Rapid refrigerant discharge
When the air conditioning system is involved in
accident damage and the circuit is punctured, the
refrigerant is discharged rapidly. The rapid discharge
of refrigerant will also result in the loss of most of the
oil from the system. The compressor must be
removed and all the remaining oil in the compressor
drained and refilled as follows:
1.Gravity drain all the oil, assist by rotating the
clutch plate (not the pulley).
2.Refill the compressor with 90ml of new
refrigerant oil.
3.Plug the inlet and outlet ports.
Servicing Equipment
The following equipment is required for full servicing
of the air conditioning system.
Recovery, recycling and charging station
Leak detector
Thermometer +20°C to -60°C
Safety goggles and gloves
Page 378 of 455

AIR CONDITIONING
3
ADJUSTMENT REFRIGERANT RECOVERY, RECYCLING,
RECHARGING
WARNING: The air conditioning system is
charged with a high pressure, potentially
toxic refrigerant. Repairs or servicing must
only be carried out by an operator familiar with
both the vehicle system and the charging and
testing equipment.
All operations must be carried out in a
well-ventilated area away from open flame and
heat sources.
Always wear safety goggles and gloves when
opening refrigerant connections.
WARNING: Wear eye and hand safety
protection. Open connections slowly in
case liquid or pressure is present. Allow to
bleed off slowly.
CAUTION: Overcharging air conditioning
system will cause excessive head
pressure.
An air conditioning portable Refrigerant Recovery
Recycling Recharging Station for use with R134a
refrigerant incorporates all the features necessary to
recover refrigerant R134a from the air conditioning
system, to filter and remove moisture, to evacuate and
recharge with the reclaimed refrigerant. The unit can
also be used for performance testing and air
conditioning system analysis.
The operator must adhere to the equipment
manufacturers' instructions.
Recovery and recycling
1.Connect a Refrigerant Station to the high and
low pressure servicing connections.
2.Operate the refrigerant recovery system
according to the manufacturers instructions.
3.Measure the amount of oil discharged from the
system. Add an equal amount of new refrigerant
oil to compressor before evacuation sequence.
WARNING: Refrigerant must always be
recycled before reuse, to ensure that the
purity of the refrigerant is high enough for
safe use in the air conditioning system. Recycling
should always be carried out with equipment
which is design certified by Underwriter
Laboratory Inc. for compliance with SAE-J1991.
Other equipment may not recycle refrigerant to
the required level of purity.
A R134a Refrigerant Recovery Recycling
Recharging Station must not be used with any
other type of refrigerant.
Refrigerant R134a from domestic and commercial
sources must not be used in motor vehicle air
conditioning systems.
Evacuation and recharging
1.Add refrigerant oil to compressor if necessary.
2.Renew the receiver/drier.
CAUTION: When a major repair has been
carried out, a leak test should be carried
out using inert gas.
3.Connect a Refrigerant Station to the high and
low pressure servicing connections.
CAUTION: Whenever the refrigerant
system is opened, the receiver/drier must
be renewed immediately before evacuating
and recharging the system.
4.Operate the refrigerant evacuation system
according to the manufactures instructions.
NOTE: If the vacuum reading is below
700mmHg after 15 minutes, suspect a leak
in the system. Partially recharge the
system and check for leaks using an electronic
leak tester. Check suction lines first, then run the
compressor for 5 minutes and then check the high
pressure lines.
CAUTION: The system must be Evacuated
immediately before recharging
commences. Delay between Evacuation
and Recharging is not permitted.
Page 379 of 455

82AIR CONDITIONING
4
ADJUSTMENT 5.Operate the refrigerant recharging system
according to the manufactures instructions.
Refrigerant to charge system is 1.1 kg.
6.If the full charge has not been accepted by the
system, start the engine and run it at 1500
rev/min for a minimum of 2 minutes.
Switch on the air conditioning system, open the
vehicle windows, set the temperature control to
cold and switch the blower to maximum speed.
7.Consult Refrigerant Station Manual for correct
procedure to complete the charge.
8.Carry out the air conditioning system
performance test.LEAK TEST SYSTEM
The following instructions refer to an electronic type
Refrigerant Leak Detector for use with R134a, which
is the safest and most sensitive.
CAUTION: When a major repair has been
carried out, a leak test should be carried
out using an inert gas (see below).
1.Place the vehicle in a well ventilated area but
free from draughts, as leakage from the system
could be dissipated without detection.
2.Follow the instructions issued by the
manufacturer of the particular leak detector
being used.
3.Commence searching for leaks by passing the
detector probe around all joints and components,
refrigerant gas is heavier than air.
4.Insert the probe into an air outlet of the
evaporator or into the evaporator drain tube.
Switch the air conditioning blower on and off at
intervals of ten seconds. Any leaking refrigerant
will be gathered in by the blower and detected.
5.Insert the probe between the magnetic clutch
and compressor to check the shaft seal for
leaks.
6.Check all service valve connections, valve plate,
head and base plate joints and back seal plate.
7.Check the condenser for leaks at the pipe
unions.
8.If any leaks are found, the system must be
discharged before rectification.
9.Rectify any leaks and recheck for leaks during
evacuation prior to charging.
Leak test using inert gas
Use Nitrogen or Helium gas.
1.Connect gas line to recharging station.
2.Pressurise system to 3 bar.
3.Carry out leak test as above.
Page 380 of 455

AIR CONDITIONING
5
ADJUSTMENT AIR CONDITIONING SYSTEM - PERFORMANCE
TEST
WARNING: R134a is hazardousSee
Repair, General Precautions
Carry out this test with bonnet and doors or windows
open, air conditioning switched on, temperature
control set to cold and blower at maximum speed. Set
the air supply control to supply fresh air.
1.Close low pressure valve on refrigerant station.
2.Close high pressure valve on refrigerant station.
3.Connect a Refrigerant Station to the high and
low pressure servicing connections.4.Insert dry bulb thermometer into cold air outlet
and position dry and wet bulb thermometer close
to outside air inlet.
Do not spill water from the wet thermometer
(psychrometer).
5.Start engine and run it at 1500 rev/min for 10
minutes with air conditioning switched on.
6.Read both pressure gauges and thermometers.
Check readings against table below with
humidity between 60% and 80%.
7.Switch off air conditioning, stop engine,
disconnect test equipment.
Performance range
Intake temperature Outlet temperature Low pressure High pressure
20 - 24°C4-10°C 18 - 28 lbf/in
2213 - 299 lbf/in2
1.2 - 1.9 bar 14.7 - 20.6 bar
25 - 29°C9-19°C 27 - 37 lbf/in2256 - 341 lbf/in2
1.9 - 2.6 bar 17.6 - 23.5 bar
30 - 35°C20-27°C 33 - 47 lbf/in2299 - 384 lbf/in2
2.3 - 3.2 bar 20.6 - 26.5 bar
Table 1
Ambient Compound Gauge High Pressure
Temperature Readings Gauge Readings
°C°F bar lbf/in
2bar lbf/in2
16 60 1,03-1,4 15-20 6,9-10,3 100-150
26,7 80 1,4-1,72 20-25 9,6-13,1 140-190
38 100 1,72-2,1 25-30 12,4-15,5 180-225
43,5 110 2,1-2,4 30-35 14,8-17,2 215-250
Page 381 of 455

82AIR CONDITIONING
6
ADJUSTMENT SYSTEM TEST
1.Place the vehicle in a ventilated, shaded area
free from excessive draught, with the doors and
windows open.
2.Check that the surface of the condenser is not
restricted with dirt, leaves, flies, etc. Do not
neglect to check the surface between the
condenser and the radiator. Clean as necessary.
3.Switch on the ignition and the air conditioner air
flow control. Check that the blower is operating
efficiently at low, medium and high speeds.
Switch off the blower and the ignition.
4.Check that the evaporator condensate drain
tubes are open and clear.
5.Check the tension of the compressor driving belt,
and adjust if necessary.
6.Inspect all connections for the presence of
refrigerant oil. If oil is evident, check for leaks,
and repair as necessary.
NOTE: The compressor oil is soluble in
Refrigerant R134a and is deposited when
the refrigerant evaporates from a leak.
7.Start the engine.
8.Set the temperature controls to cold and switch
the air conditioner blower control on and off
several times, checking that the magnetic clutch
on the compressor engages and releases each
time.
9.With the temperature control at maximum
cooling and the blower control at high speed,
warm up the engine and fast idle at 1000
rev/min.
10.Repeat at 1800 rev/min.
11.Gradually increase the engine speed to the high
range and check the sight glass at intervals.
12.Check for frosting on the service valves.
13.Check the high pressure hoses and connections
by hand for varying temperature. Low
temperature indicates a restriction or blockage at
that point.
14.Switch off the air conditioning blower and stop
the engine.
15.If the air conditioning equipment is still not
satisfactory, carry out a pressure test as
previously described in this section.PRECAUTIONS IN HANDLING REFRIGERANT
LINES
WARNING: Wear eye and hand protection
when disconnecting components
containing refrigerant. Plug all exposed
connections immediately.
1.When disconnecting any hose or pipe
connection the system must be discharged of all
pressure. Proceed cautiously, regardless of
gauge readings. Open connections slowly,
keeping hands and face well clear, so that no
injury occurs if there is liquid in the line. If
pressure is noticed, allow it to bleed off slowly.
2.Lines, flexible end connections and components
must be capped immediately they are opened to
prevent the entrance of moisture and dirt.
3.Any dirt or grease on fittings must be wiped off
with a clean alcohol dampened cloth. Do not use
chlorinated solvents such as trichloroethylene. If
dirt, grease or moisture cannot be removed from
inside the hoses, they must be replaced with
new hoses.
4.All replacement components and flexible end
connections must be sealed, and only opened
immediately prior to making the connection.
5.Ensure the components are at room temperature
before uncapping, to prevent condensation of
moisture from the air that enters.
6.Components must not remain uncapped for
longer than 15 minutes. In the event of delay, the
caps must be fitted.
7.Receiver/driers must never be left uncapped as
they contain Silica Gel crystals which will absorb
moisture from the atmosphere. A receiver/ drier
left uncapped must not be used, fit a new unit.
8.The compressor shaft must not be rotated until
the system is entirely assembled and contains a
charge of refrigerant.
9.A new compressor contains an initial charge of
refrigerant oil. The compressor also contains a
holding charge of gas when received which
should be retained by leaving the seals in place
until the pipes are re-connected.
10.The receiver/drier should be the last component
connected to the system to ensure optimum
dehydration and maximum moisture protection of
the system.
Page 382 of 455

AIR CONDITIONING
7
ADJUSTMENT 11.All precautions must be taken to prevent
damage to fittings and connections. Slight
damage could cause a leak with the high
pressures used in the system.
12.Always use two wrenches of the correct size,
one on each fitting when releasing and
tightening refrigeration unions.
13.Joints and 'O' rings should be coated with
refrigeration oil to aid correct seating. Fittings
which are not lubricated with refrigerant oil are
almost certain to leak.
14.All lines must be free of kinks. The efficiency of
the system is reduced by a single kink or
restriction.
15.Flexible hoses should not be bent to a radius
less than 90mm radius.
16.Flexible hoses should not be within 100mm of
the exhaust manifold.
17.Completed assemblies must be checked for
refrigeration lines touching metal panels. Any
direct contact of lines and panels transmits noise
and must be eliminated.PERIODIC MAINTENANCE
Routine servicing, apart from visual checks, is not
necessary. The visual inspections are as follows:
Condenser
With a water hose or air line, clean the fins of the
condenser to remove flies, leaves, etc. Check the pipe
connections for signs of oil leakage.
Compressor
Check pipe connections for signs of oil leakage.
Check flexible hoses for swelling. Examine the
compressor belt for tightness and condition.
Sight glass
Examine the sight glass for bubbles with the system
operating. Check connections for leakage.
Evaporator
Examine the refrigeration connections at the unit.
Page 383 of 455

AIR CONDITIONING
1
REPAIR COMPRESSOR
Service repair no - 82.10.20
Remove
1.Disconnect battery.
2.Recover refrigerant from air conditioning system
See Adjustment, Refrigerant recovery,
recycling, recharging.
3.Remove compressor drive belt.See
Compressor drive belt
4.Disconnect high pressure pipe from compressor.
5.Disconnect low pressure pipe from compressor.
6.Remove 'O' ring from each flange.
7.Disconnect compressor clutch harness
multi-plug.
8.Remove compressor from mounting bracket
studs.Refit
9.If a new compressor is to be fitted first drain oil
from new compressor. Drain and measure oil
from old compressor. Measure new oil equal to
amount from old compressor, add 30 ml extra to
this amount and refill new compressor through
outlet port.
10.Locate compressor over mounting bracket studs.
11.Reconnect compressor clutch harness
multi-plug.
12.Fit new 'O' rings to high and low pressure hose
flanges, lubricate with refrigerant oil.
13.Fit high and low pressure hoses.
14.Fit compressor drive belt
See Compressor
drive belt.
15.Evacuate and recharge air conditioning system
See Adjustment, Refrigerant recovery,
recycling, recharging.
16.Reconnect battery.
17.Perform a leak test on disturbed joints.
18.Carry out a functional check.
Page 384 of 455
82AIR CONDITIONING
2
REPAIR COMPRESSOR DRIVE BELT
Service repair no - 82.10.02
Remove
1.Disconnect battery.
2.Remove auxiliary drive belt
See ELECTRICAL,
Repair, Auxiliary drive belt.
3.Remove 3 nuts securing drive belt guard to
compressor retaining studs.
4.Slacken 3 belt tensioner retaining bolts.
5.Remove compressor drive belt. Mark direction
on belt if refitting.Refit
6.Fit compressor drive belt.
7.Fit drive belt guard.
8.Fit torque meter to centre of tensioner, apply and
hold a torque of
35 Nm (26 lbf/ft).
9.Tighten tensioner retaining bolts.
10.Rotate crankshaft 2 full turns.
11.Reapply and hold a torque of
35 Nm (26 lbf/ft)
to tensioner, then fully slacken and retighten
tensioner retaining bolts to
25 Nm (18 lbf/ft).
12.Fit auxiliary drive beltSee ELECTRICAL,
Repair, Auxiliary drive belt.
13.Reconnect battery.