Page 1329 of 1378
![JEEP CHEROKEE 1988 Service Repair Manual CURRENT WAVEFORM SAMPLES
EXAMPLE #1 - VOLTAGE CONTROLLED DRIVER
The waveform pattern shown in Fig. 4 indicate a normal
current waveform from a Ford 3.0L V6 VIN [U] engine. JEEP CHEROKEE 1988 Service Repair Manual CURRENT WAVEFORM SAMPLES
EXAMPLE #1 - VOLTAGE CONTROLLED DRIVER
The waveform pattern shown in Fig. 4 indicate a normal
current waveform from a Ford 3.0L V6 VIN [U] engine.](/manual-img/16/57037/w960_57037-1328.png)
CURRENT WAVEFORM SAMPLES
EXAMPLE #1 - VOLTAGE CONTROLLED DRIVER
The waveform pattern shown in Fig. 4 indicate a normal
current waveform from a Ford 3.0L V6 VIN [U] engine. This voltage
controlled type circuit pulses the injectors in groups of three
injectors. Injectors No. 1, 3, and 5 are pulsed together and cylinders
2, 4, and 6 are pulsed together. The specification for an acceptable
bank resistance is 4.4 ohms. Using Ohm's Law and assuming a hot run
voltage of 14 volts, we determine that the bank would draw a current
of 3.2 amps.
However this is not the case because as the injector windings
become saturated, counter voltage is created which impedes the current
flow. This, coupled with the inherent resistance of the driver's
transistor, impedes the current flow even more. So, what is a known
good value for a dynamic current draw on a voltage controlled bank of
injectors? The waveform pattern shown below indicates a good parallel
injector current flow of 2 amps. See Fig. 4.
Note that if just one injector has a resistance problem and
partially shorts, the entire parallel bank that it belongs to will
draw more current. This can damage the injector driver.
The waveform pattern in Fig. 5 indicates this type of problem
with too much current flow. This is on other bank of injectors of the
same vehicle; the even side. Notice the Lab Scope is set on a one amp
per division scale. As you can see, the current is at an unacceptable
2.5 amps.
It is easy to find out which individual injector is at fault.
All you need to do is inductively clamp onto each individual injector
and compare them. To obtain a known-good value to compare against, we
used the good bank to capture the waveform in Fig. 6. Notice that it
limits current flow to 750 milliamps.
The waveform shown in Fig. 7 illustrates the problem injector
we found. This waveform indicates an unacceptable current draw of just
over one amp as compared to the 750 milliamp draw of the known-good
injector. A subsequent check with a DVOM found 8.2 ohms, which is
under the 12 ohm specification.
Fig. 4: Injector Bank w/Normal Current Flow - Current Pattern
Page 1331 of 1378
![JEEP CHEROKEE 1988 Service Repair Manual EXAMPLE #2 - VOLTAGE CONTROLLED DRIVER
This time we will look at a GM 3.1L V6 VIN [T]. Fig. 8 shows
the 1, 3, 5 (odd) injector bank with the current waveform indicating
about a 2.6 JEEP CHEROKEE 1988 Service Repair Manual EXAMPLE #2 - VOLTAGE CONTROLLED DRIVER
This time we will look at a GM 3.1L V6 VIN [T]. Fig. 8 shows
the 1, 3, 5 (odd) injector bank with the current waveform indicating
about a 2.6](/manual-img/16/57037/w960_57037-1330.png)
EXAMPLE #2 - VOLTAGE CONTROLLED DRIVER
This time we will look at a GM 3.1L V6 VIN [T]. Fig. 8 shows
the 1, 3, 5 (odd) injector bank with the current waveform indicating
about a 2.6 amp draw at idle. This pattern, taken from a known good
vehicle, correctly stays at or below the maximum 2.6 amps current
range. Ideally, the current for each bank should be very close in
comparison.
Notice the small dimple on the current flow's rising edge.
This is the actual injector opening or what engineers refer to as the
"set point." For good idle quality, the set point should be uniform
between the banks.
When discussing Ohm's Law as it pertains to this parallel
circuit, consider that each injector has specified resistance of 12.2
ohms. Since all three injectors are in parallel the total resistance
of this parallel circuit drops to 4.1 ohms. Fourteen volts divided by
four ohms would pull a maximum of 3.4 amps on this bank of injectors.
However, as we discussed in EXAMPLE #1 above, other factors knock this
value down to roughly the 2.6 amp neighborhood.
Now we are going to take a look at the even bank of
injectors; injectors 2, 4, and 6. See Fig. 9. Notice this bank peaked
at 1.7 amps at idle as compared to the 2.6 amps peak of the odd bank (
Fig. 8 ). Current flow between even and odd injectors banks is not
uniform, yet it is not causing a driveability problem. That is because
it is still under the maximum amperage we figured out earlier. But be
aware this vehicle could develop a problem if the amperage flow
increases any more.
Checking the resistance of this even injector group with a
DVOM yielded 6.2 ohms, while the odd injector group in the previous
example read 4.1 ohms.
Fig. 8: Injector Odd Bank w/Normal Current Flow - Current Pattern
Page 1332 of 1378
Fig. 9: Injector Even Bank w/Normal Current Flow - Current Pattern
EXAMPLE #3 - VOLTAGE CONTROLLED DRIVER
Example #3 is of a Ford 5.0L V8 SEFI. Fig. 10 shows a
waveform of an individual injector at idle with the Lab Scope set on
200 milliamps per division. Notice the dimple in the rising edge. This
dimple indicates the actual opening of the injector (set point)
occurred at 400 milliamps and current peaked at 750 milliamps. This is
a good specification for this engine.
The next waveform pattern in Fig. 11 shows an abnormality
with another injector. With the Lab Scope set on 500 milliamps per
division, you can see that the current waveform indicates a 1200
milliamp draw. This is a faulty injector.
Abnormally low resistance injectors create excessive current
draw, causing rough idle, and possible computer driver damage.
Fig. 10: Single Injector w/Normal Current Flow - Current Pattern
Page 1334 of 1378
PFI VIN [3]. It is a perfect example of the peak and hold theory. The
waveform shows a 1-amp per division current flow, ramping to 4 amps
and then decreasing to 1-amp to hold the injector open.
Fig. 13: Injector Bank w/Normal Current Flow - Current Pattern
EXAMPLE #6 - CURRENT CONTROLLED DRIVER
This next known-good waveform is from a Ford 5.0L V8 CFI VIN
[F]. See Fig. 14. The pattern, which is set on a 250 milliamps scale,
indicates a 1.25 amp peak draw and a hold at 350 milliamps.
Fig. 14: Single Injector w/Normal Current Flow - Current Pattern
EXAMPLE #7 - CURRENT CONTROLLED DRIVER
The known-good current controlled type waveform in Fig. 15 is
from a GM 2.0L TBI VIN [1]. With the lab scope set at 2 amps per
division, notice that this system peaks at 4 amps and holds at 1 amp.
The next waveform is from the same type of engine, except
Page 1336 of 1378
Fig. 17: Single Injector w/Normal Current Flow - Current Pattern
VOLTAGE WAVEFORM SAMPLES
EXAMPLE #1 - VOLTAGE CONTROLLED DRIVER
These two known-good waveform patterns are from a Ford 4.6L
V8 VIN [W]. Fig. 18 illustrates the 64 volt inductive kick on this
engine, indicating no clamping is occurring. The second pattern,
Fig. 19 , was taken during hot idle, closed loop, and no load.
Page 1340 of 1378
Fig. 21: Injector Bank - Known Good - Voltage Pattern
EXAMPLE #4 - CURRENT CONTROLLED DRIVER
From 1984 to 1987, Chrysler used this type injector drive on
their TBI-equipped engines. See Fig. 22 for a known-good pattern.
Instead of the ground side controlling the injector, Chrysler
permanently grounds out the injector and switches the power feed side.
Most systems do not work this way.
These injectors peak at 6 amps of current flow and hold at 1
amp.
Page 1341 of 1378
Fig. 22: Single Injector - Known Good - Voltage Pattern
EXAMPLE #5 - CURRENT CONTROLLED DRIVER
These two known-good waveform patterns are from a Chrysler 3.
0L V6 VIN [3]. The first waveform, Fig. 23, is a dual trace pattern
that illustrates how Chrysler uses the rising edge of the engine speed
signal to trigger the injectors. The second waveform, Fig. 24, was
taken during hot idle, closed loop, and no load.
Page 1359 of 1378

\003
WIP ER /W ASH ER S YSTE M
1988 J e ep C hero ke e
1988 Wiper/Washer Systems
JEEP
All Models
DESCRIPTION
Jeep vehicles use a 2-speed electric motor, which is a
compound wound (series and shunt) type. A crank arm, attached
externally to gear shaft, operates linkage which activates wiper
blades.
All models have an optional intermittent feature. All models
use an electric washer system consisting of a motor, reservoir, and
necessary hoses and nozzles.
Some Cherokee and Wagoneer models are equipped with rear
wipers. The rear motor is a single-speed motor with an automatic park
feature. The circuit is protected by a separate 4.5-amp circuit
breaker attached to brake pedal support.
TROUBLE SHOOTING
WIPER INOPERATIVE OR OPERATES AT ONE SPEED ONLY
1) If wiper does not operate on either speed, check for
binding or interference of linkage. If okay, place wiper switch on
"LO" and then on "HI" setting. Connect a test light between terminals
of wiring harness plug that connects to motor.
2) Check for power at White wire with tracer and Black
(ground) wire terminal for low speed. Check between Dk. Blue with
tracer and Black wire terminal for high speed.
3) If light does not glow, check ignition switch, wiper
switch, harness or terminals for open circuits. If light glows, check
for loose or misaligned connection between wiring harness plug and
motor plug. If okay, replace wiper motor.
WIPERS DO NOT PARK
1) Disconnect motor and connect Gray lead to White lead.
Apply 12 volts to Blue lead. Replace motor if it fails to park. If it
parks, turn ignition switch on, and wiper switch to "PARK".
2) Connect a test light to Lt. Green wire with tracer and to
ground at motor plug.
3) Check continuity between Tan wire with tracer and White
wire with tracer.
4) If test light does not glow, check harness connections
between motor and instrument panel switch. If okay, replace panel
switch. If not okay, repair harness connection.
WIPER MOTOR QUITS WHILE WIPING
1) With engine idling and blower motor on high, operate
wipers at high speed setting for 5 cycles consisting of 3 seconds of
water and 57 seconds of drying.
2) If motor struggles to a complete stop, clean glass and
replace blades. Repeat test. If motor stops, test circuit breaker in
panel switch. If motor stopped suddenly in original test, check
circuit breaker. Repeat test. If motor stops, replace motor.