62B - 37
CLIMATE CONTROL
Fault finding – Conformity check62B
V3 MR-372-J84-62B000$090.mif
Vdiag No.: 44
COLD LOOP SUB-FUNCTION
NOTESOnly carry out this conformity check after a full check with the diagnostic tool (fault
reading and configuration checks).
Test conditions: engine off, ignition on (forced 12 V After ignition).
Air conditioning off (air conditioning compressor not triggered).
Special note:
The various conformity checks
for the air conditioning function are explained in the
Introduction section.
Order FunctionParameter or Status
checked or Action Display and Notes Fault finding
1Request to
engage the
compressorET143:Air conditioning
request 1ACTIVE for air
conditioning request
(AC button pressed or
AUTO button pressed
with maximum cold
request).
INACTIVE the
opposite.If there is a fault, refer to the
fault finding procedure
for this status.
Note: This status
represents the request from
the climate control
computer to the UCH to
switch on the compressor
(refer to the flowchart in the
system operation section).
2TemperaturePR001:Interior
temperatureX = interior
temperature ± 5 ˚C
(invalid value: 87.5 ˚C)If there is a fault, refer to the
fault finding procedure
for this parameter.
3Passenger
compartment
blowerET141:Passenger
compartment
blowerRUNNING
or
STORED
depending on user
requestIf there is a fault, refer to the
fault finding procedure
for this status.
4Air flapPR012:Mixing flap
position0% = Max cold
position (15 ˚C)
100% = Max hot
position (27 ˚C)If there is a fault, refer to the
fault finding procedure
for this parameter.
5Solar radiationPR006:Solar radiationfrom 0 W (no sunlight)
to 400 W (maximum
sunlight).
(invalid value: 765 W)If there is a fault, refer to the
fault finding procedure
for this parameter.
ACREG X84 1.1
Edition 2
62B - 40
CLIMATE CONTROL
Fault finding – Conformity check62B
V3 MR-372-J84-62B000$090.mif
Vdiag No.: 44
MAIN SCREEN
NOTESOnly carry out this conformity check after a full check with the diagnostic tool (fault
reading and configuration checks).
Test conditions: engine off, ignition on (forced 12 V After ignition).
Air conditioning off (air conditioning compressor not triggered).
Special note:
The various conformity checks for the air conditioning function are explained in the
Introduction section.
Note:
This page lists the statuses and parameters provided by the climate control computer
but which are not associated with the four sub-functions given in the conformity check
(PASSENGER COMPARTMENT VENTILATION, COLD LOOP, USER SELECTION
and HEATING sub-functions).
Order FunctionParameter or Status
checked or Action Display and Notes Fault finding
1Electrical
suppliesPR092:Battery voltage10.5 < X < 14.4 VIn the event of a fault, see
the interpretation of this
parameter
ET007:+ after ignition
computer feedABSENT: Ignition off.
PRESENT: Ignition on.In the event of a fault, refer
to the interpretation of
this status.
ET002:+ 12 V side
lightsABSENT: Side lights
off.
PRESENT: Side lights
on.In the event of a fault,
consult the interpretation
of this status (see 87B,
Passenger compartment
connection unit).
PR122:Night-time
lighting level6% = minimum lighting
level.
99% = maximum
lighting level.
(side lights off: 102%)In the event of a fault, refer
to the interpretation of
parameter PR111 Lighting
dimmer voltage (see 83A,
Instrument panel).
ACREG X84 1.1
Edition 2