1B-28 AIR CONDITIONING (OPTIONAL)
8) After the system has been charged with specified amount of re-
frigerant or when low pressure gauge (1) and high pressure
gauge (2) have indicated about 2 and 15 kg / cm
2 respectively,
close low pressure side vale (3) of manifold gauge set (4). If
equipped with sight glass in this time, look into the sight glass (6)
of condenser outlet pipe (5) and check that there are no bubbles
(7) in it, which means that the system is fully charged.
Low pressure gauge when charged with specified amount:
About 200 ± 300 kPa (2 ± 3 kg / cm
2, 29 ± 43 psi)
(At A / C inlet temperature 30 ± 35C, 86 ± 95F)
High pressure gauge when charged with specified amount:
About 1370 ± 1670 kPa (14 ± 17 kg / cm
2, 200 ± 244 psi)
(At A / C inlet temperature 30 ± 35C, 86 ± 95F)
Page 100 of 801

YH4
GRAND
VITARA
1. Electric leak detector
AIR CONDITIONING (OPTIONAL) 1B-29
REMOVING MANIFOLD GAUGE SET
When A / C system has been charged with a specified amount of re-
frigerant, remove manifold gauge set as follows:
1) Close low pressure-side valve of manifold gauge set, (The high
pressure-side valve is closed continuously during the process
of charging.).
2) Close refrigerant container valve.
3) Stop engine.
4) Using shop rag, remove charging hoses from service valves.
This operation must be performed rapidly.
WARNING:
High pressure-side is naturally under high pressure.
So, care must be used to protect your eyes and skin.
5) Put caps on service valves.
LEAK-TESTING REFRIGERANT SYSTEM
Whenever a refrigerant leak is suspected in the system or any ser-
vice operation has been performed which may result in disturbing
lines or connections, it is advisable to test for leaks.
Common sense should be used in performing any refrigerant leak
test, since the need and extent of any such test will, in general, de-
pend upon the nature of a complaint and the type of a service per-
formed on the system.
LIQUID LEAK DETECTORS
There are a number of fittings and places throughout the air condi-
tioning system where a liquid leak detector solution may be used
to pinpoint refrigerant leaks.
By merely applying the solution to the area in question with a swab,
bubbles will form within seconds if there is a leak.
For confined areas, such as sections of the evaporator and con-
denser, an electronic (gas) leak detector is more practical for deter-
mining leaks.
WARNING:
To prevent explosions or fires, make sure that there are no
flammables in the vicinity.
When exposed to fire, the refrigerant turns into a poison-
ous gas (phosgene). Do not inhale this gas.
Page 101 of 801

YH4
GRAND
VITARA
1. Suction hose
2. Discharge hose
3. Liquid pipe
4. Condenser outlet pipe
5. Expansion valve
6. Dual pressure switch
7. Suction pipe
: Apply compressor oil
(refrigerant oil) to O-ring.
1B-30 AIR CONDITIONING (OPTIONAL)
ON-VEHICLE SERVICE
WARNING:
Should refrigerant HFC-134a (R-134a) strike your eye(s), consult a doctor immediately.
DO NOT USE YOUR HAND TO RUB AFFECTED EYE(S).
Instead, use quantities of fresh cold water to splash it over affected area to thus gradually raise its
temperature above the freezing point.
Obtain proper treatment as soon as possible from a doctor or eye specialist.
Should liquid refrigerant HFC-134a (R-134a) get on your skin, such affected part should be treated
in the same manner as when skin is frostbitten or frozen.
CAUTION:
None of refrigerant, compressor oil and component parts is interchangeable between two types of A / C:
one using CFC-12 (R-12) and the other using HFC-134a (R-134a).
(For identification between these two types, refer to page 1B-2).
When replenishing or changing refrigerant and compressor oil and when replacing parts, make sure
that the material or the part to be used is appropriate to the A / C installed in the vehicle being serviced.
Use of incorrect one will result in leakage of refrigerant, damage in parts or other faulty condition.
PRECAUTION
When servicing air conditioning system, the following rules must be observed.
PIPING
When connecting hoses and pipes, apply a few drops of compressor oil (refrigerant oil) to seats of coupling nuts
and O-ring.
Never use heat for bending pipes. When bending a pipe, try to make its bending radius as slight as possible.
Keep internal parts of air conditioning free from moisture and dirt. When disconnecting any line from system,
install a blind plug or cap to the fitting immediately.
When tightening or loosening a fitting, use two wrenches, one for turning and the other for support.
Page 102 of 801

YH4
GRAND
VITARA
AIR CONDITIONING (OPTIONAL) 1B-31
Tighten flared nuts to specified torque.
Tightening Torque (Flared Nut Used for)
8 mm pipe: 13 N
.m (1.3 kg-m, 9.5 lb-ft)
14.5 mm pipe: 23 N
.m (2.3 kg-m, 16.6 lb-ft)
16 mm pipe: 33 N
.m (3.3 kg-m, 23.8 lb-ft)
Route drain hose so that drained water does not make any contact to vehicle components.
HANDLING REFRIGERANT HFC-134a (R-134a)
When handling refrigerant, always wear goggles to protect your eyes.
Avoid you direct contact to liquid refrigerant.
Do not heat refrigerant container higher than 40C (104F).
Do not discharge refrigerant into atmosphere.
Do not allow liquid refrigerant to touch bright metals. Refrigerant combined with moisture is corrosive and will
tarnish surfaces of bright metals including chrome.
After recovering refrigerant from system, the amount of compressor oil removed must be measured and the same
amount added to the system.
REFRIGERANT RECOVERY
When discharging refrigerant out of A / C system, always recover it by using refrigerant recovery and recycling
equipment. Discharging refrigerant HFC-134a (R-134a) into atmosphere would cause adverse effect to environ-
ments.
NOTE:
When handling recovery and recycling equipment, be sure to follow the instruction manual for the equip-
ment.
REFRIGERANT CHARGE
Charge a proper amount of refrigerant to A / C system according to charging procedure described in recovery, evac-
uation and charging.
CAUTION:
Do not perform an additional refrigerant charging to A / C system. This cause it to overcharge.
Page 104 of 801

YH4
GRAND
VITARA
2. Bolt
For CAMI production vehicle
For IWATA production vehicle
AIR CONDITIONING (OPTIONAL) 1B-33
A / C CONDENSER ASSEMBLY
INSPECTION
Check
a) condenser fins for blockage
b) condenser fittings for leakage
c) condenser fins for damage
Clogged condenser fins should be washed with water, and should
be dried with compressed air.
CAUTION:
Be careful not to damage condenser fins. If condenser fin is
bent, straighten it by using a screwdriver or pair of pliers. If
any leakage is found from fitting or tube, repair or replace
condenser.
REMOVAL
1) Disconnect negative (±) cable at battery.
2) Recover refrigerant by using recovery and recycling equipment.
Be sure to follow the instruction manual for the equipment.
The amount of compressor oil removed must be measured and
the same amount added to the system.
3) Remove front bumper assembly and remove lower stay (1) if
equipped (Refer to Section 9 ªBODY SERVICEº).
4) Disconnect compressor discharge hose (1) from condenser in-
let fittings.
CAUTION:
As soon as above hose and pipe are disconnected, cap
opened fittings so that moisture and dust do not enter
condenser.
Page 105 of 801
YH4
GRAND
VITARA
3
1B-34 AIR CONDITIONING (OPTIONAL)
5) Disconnect coupler from dual pressure switch (1).
6) Disconnect condenser outlet pipe (3).
7) Disconnect condenser cooling fan motor coupler (2).
8) Remove condenser with fan.
NOTE:
Be careful not to damage fins of condenser and radiator.
9) Remove A / C condenser cooling fan assembly from condenser.
INSTALLATION
Reverse removal sequence to install condenser, noting following
point.
1) When replacing condenser, add 20 to 30 cc of refrigerating oil
from compressor suction-side.
2) Evacuate and charge system according to previously-described
procedure.
Page 106 of 801
YH4
GRAND
VITARA
1. Air flow
AIR CONDITIONING (OPTIONAL) 1B-35
CONDENSER COOLING FAN ASSEMBLY
INSPECTION
Remove condenser assembly (Refer to ªA / C CONDENSER AS-
SEMBLY REMOVALº in this section).
Check continuity between terminal to terminal as shown.
If check results are continuity, proceed to next operation check.
If not, replace.
Connect battery to condenser fan motor as shown, then check
that the condenser fan motor operates smoothly and specified
current.
Specified current: Maximum 12 A at 12 V
Page 107 of 801
YH4
GRAND
VITARA
12
2. Condenser dryer section
1B-36 AIR CONDITIONING (OPTIONAL)
CONDENSER DRYER (RECEIVER / DRYER)
REMOVAL
1) Remove A / C condenser assembly (1) from vehicle (Refer to
ªA / C CONDENSER ASSEMBLY REMOVALº in this section.).
2) Remove the condenser dryer cap from condenser.
3) Remove the filter (1) from the condenser (2).
4) Remove the dryer (1) using a plier (2).
INSTALLATION
Reverse removal sequence to install condenser dryer, according to
instruction manual with supply parts.
NOTE:
When replacing condenser dryer, add 40 cc of refrigerating
oil the same as compressor oil.
Do not remove the dryer from the plastic bag until just before
inserting it into the receiver.
Install the condenser dryer (1) with its double-layer portion
facing the bottom of the receiver.
If condenser dryer cap installing is bolt type, tighten speci-
fied torque for its bolt.
Tightening Torque:
Cap: 12.5 N
.m (1.25 kg-m, 9 lb-ft)