62B - 40
CLIMATE CONTROL
Fault finding – Conformity check62B
V3 MR-372-J84-62B000$090.mif
Vdiag No.: 44
MAIN SCREEN
NOTESOnly carry out this conformity check after a full check with the diagnostic tool (fault
reading and configuration checks).
Test conditions: engine off, ignition on (forced 12 V After ignition).
Air conditioning off (air conditioning compressor not triggered).
Special note:
The various conformity checks for the air conditioning function are explained in the
Introduction section.
Note:
This page lists the statuses and parameters provided by the climate control computer
but which are not associated with the four sub-functions given in the conformity check
(PASSENGER COMPARTMENT VENTILATION, COLD LOOP, USER SELECTION
and HEATING sub-functions).
Order FunctionParameter or Status
checked or Action Display and Notes Fault finding
1Electrical
suppliesPR092:Battery voltage10.5 < X < 14.4 VIn the event of a fault, see
the interpretation of this
parameter
ET007:+ after ignition
computer feedABSENT: Ignition off.
PRESENT: Ignition on.In the event of a fault, refer
to the interpretation of
this status.
ET002:+ 12 V side
lightsABSENT: Side lights
off.
PRESENT: Side lights
on.In the event of a fault,
consult the interpretation
of this status (see 87B,
Passenger compartment
connection unit).
PR122:Night-time
lighting level6% = minimum lighting
level.
99% = maximum
lighting level.
(side lights off: 102%)In the event of a fault, refer
to the interpretation of
parameter PR111 Lighting
dimmer voltage (see 83A,
Instrument panel).
ACREG X84 1.1
Edition 2
62B-52
CLIMATE CONTROL
Fault finding – Fault Finding Chart62B
V3 MR-372-J84-62B000$110.mif
Vdiag No.: 44
ALP 11 Unpleasant odours in the passenger compartment
NOTESOnly consult this customer complaint after a complete check using the
diagnostic tool.
Check that the cabin filter is not blocked or damaged.
Replace it if necessary.
Is the fault still present?
YES
Check that the condensation drain ring (water from the
evaporator) is not obstructed (under the body).
Repair if necessary.
Is the fault still present?
YES
Check the sealing of the heating unit in relation to the engine
compartment:
–Foam seal on the heater matrix coolant pipes fitted and in
good condition.
–Rubber seal on the radiator tank fitted and in good condition
(seal under the bonnet separating the engine compartment
from the windscreen aperture).
–Drain valve on the radiator tank fitted and in good condition.
Repair if necessary.
Is the fault still present?
YES
Remove the cabin filter to apply air conditioning system
cleaner using an extension pipe on the evaporator.
Spray the entire contents of the aerosol.
Leave the product to work for 15 minutes.
NO
NO
NOEnd of fault finding procedure.
End of fault finding procedure.
End of fault finding procedure.
AFTER REPAIRPerform a complete check using the diagnostic tool.
ACREG X84 1.1
Edition 2
62B-57
CLIMATE CONTROL
Fault finding – Fault Finding Chart62B
V3 MR-372-J84-62B000$110.mif
Vdiag No.: 44
ALP 15 Passenger compartment ventilation noises
NOTESOnly deal with this customer complaint after a full check with the diagnostic tool
(fault reading and configuration checks).
The aim of the following operations is to check and, if necessary, eliminate any foreign bodies
(leaves, insects, other, etc.) in:
–the passenger compartment air inlet,
–the cabin filter housing,
–the housing and on the fan assembly.
Check the passenger compartment air inlet and the cabin filter housing:
Remove:
–the scuttle panel grille (see MR 371 Bodywork, 55A, Exterior equipment, Scuttle panel grille: Removal -
Refitting),
–the air filter access panel,
–the scuttle panel partition,
–the cabin filter.
Check that there are no foreign bodies (leaves, insects, other, etc.) and, if necessary, clean the passenger
compartment air inlet and the cabin filter housing.
Refit:
–the cabin filter,
–the scuttle panel partition,
–the air filter access panel,
the scuttle panel grille (see MR 371 Bodywork, 55A, Exterior equipment, Scuttle panel grille: Removal -
Refitting).
Check the housing and the fan assembly:
Remove the fan assembly (see MR 370 Mechanical, 61A, Heating, Fan assembly: Removal - Refitting).
Check that there are no foreign bodies (leaves, insects, other, etc.) and, if necessary, clean the fan assembly
housing.
Check that there are no foreign bodies (leaves, insects, other, etc.) and, if necessary, clean the fan assembly.
Refit the fan assembly (see MR 370 Mechanical, 61A, Heating, Fan assembly: Removal - Refitting).
AFTER REPAIRPerform a complete check using the diagnostic tool.