YH4
GRAND
VITARA
1B-14 AIR CONDITIONING (OPTIONAL)
HIGH PRESSURE CAUGE LOW PRESSURE GAUGE THERMOMETER AT
CENTER DUCT
Insufficient
cooling of
condenser
PERFORMANCE DIAGNOSIS TABLE
TESTING RESULTSPOSSIBLE CAUSEREMEDY
Pressure high
(ªAº area of high side
graph)Refrigerant overcharged
Expansion valve frozen or clogged
Clogged refrigerant passage of high side
Condenser fan malfunction
Dirty or bent condenser fins
Compressor malfunction (Insufficient oil etc.)
Engine overheatRecharge
Check expansion valve
Clean or replace
Check condenser fan
Clean or repair
Check compressor
Check engine cooling
system
Pressure low
(ªBº area of high side
graph)Insufficient refrigerant (Insufficient charge or
leakage)
Expansion valve malfunction (Valve opens too
wide)
Compressor malfunction (Insufficient
compression)Check for leakage, repair if
necessary and recharge
Check expansion valve
Check compressor
Pressure high
(ªAº area of low side
graph)Expansion valve malfunction (Valve opens too
wide)
Compressor malfunction (Insufficient
compression)Check expansion valve
Check compressor
Pressure low
(ªBº area of low side
graph)Insufficient refrigerant (Insufficient charge or
leakage)
Expansion valve malfunction (Valve opens too
narrow)
Clogged refrigerant passage (Crashed pipe)Check for leakage, repair if
necessary and recharge
Check expansion valve
Repair or replace
Outlet air temperature
at center duct is high
(Crossing point is in
area ªAº)Insufficient or excessive charge of refrigerant
Dirty or bent evaporator fins
Air leakage from cooling (heater) unit or air
duct
Malfunctioning, switchover function of damper
in cooling (heater) unit
Compressor malfunctionCheck refrigerant
pressure
Clean or repair
Repair or replace
Repair or replace
Check compressor
Outlet air temperature
at center duct is low
(Crossing point is in
area ªBº)Insufficient air volume from center duct
(Heater blower malfunction)
Compressor malfunctionCheck blower motor and
fan
Check compressor
NOTE:
If ambient temperature is within 30 ± 35C (85 ± 95F), it is possible to do using next page table for more
detail diagnosis.
YH4
GRAND
VITARA
AIR CONDITIONING (OPTIONAL) 1B-15
AMBIENT TEMPERATURE WITHIN 30 ± 35C (85 ± 95F)
CONDITION
MANIFOLD
GAUGEMPa
(kg/cm2)
(psi)DETAILCAUSECORRECTION
LoHi
0.23 ± 0.35
(2.3 ± 3.5)
(33 ± 50)1.4 ± 1.75
(14 ± 17.5)
(200 ± 249)
Normal condition.ÐÐÐÐ
Negative
pressure0.5 ± 0.6
(5 ± 6)
(71.2 ± 85.3)
The low pressure side
reads a negative pressure,
and the high pressure side
reads an extremely low
pressure.
Presence of frost around
tubing to and from receiver /
dryer and expansion valve. Dust particles or water
droplets are either stuck or
frozen inside expansion
valve, preventing the
refrigerant from flowing.Clean expansion valve.
Replace it if it cannot be
cleaned.
Replace receiver / dryer.
Evacuate the A / C
system and recharge
with fresh refrigerant.
Normal:
0.23 ± 0.35
(2.3 ± 3.5)
(33 ± 50)
Abnormal:
Negative
pressureNormal:
1.4 ± 1.75
(14 ± 17.5)
(200 ± 249)
Abnormal:
0.69 ± 0.98
(7 ± 10)
(100 ± 142) During A / C operation, the
low pressure side
sometimes indicates
negative pressure, and
sometimes normal
pressure. Also high
pressure side reading
fluctuates between the
abnormal and normal
pressure.Expansion valve is frozen
due to moisture in the
system, and temporarily
shuts off the refrigeration
cycle.Replace expansion
valve.
Replace receiver / dryer.
Evacuate A / C system
and recharge with fresh
refrigerant.
0.05 ± 0.15
(0.5 ± 1.5)
(4.2 ± 21.3)
0.69 ± 0.98
(7 ± 10)
(100 ± 142)
Both low and high pressure
sides indicate low readings.
Continuous air bubbles are
visible through sight glass.
Output air is slightly cold.Insufficient refrigerant in
system. (Refrigerant
leaking)Using a gas leak
detector, check for leaks
and repair as necessary.
Recharge refrigerant to a
specified amount.
If the pressure reading is
almost 0 when the
manifold gauges are
attached, check for any
leaks, repair them, and
evacuate the system.
0.4 ± 0.6
(4 ± 6)
(56.9 ± 85.3)
Pressure on low pressure
side is high.
Pressure on high pressure
side is low.
Both pressure becoming
equal right after A / C is
turned OFF.Internal leak in compressor.Inspect compressor and
repair or replace as
necessary.
035 045
High pressure reading on
both low and high pressure
sides.
Air bubbles are not visible
even when engine rpm is
lowered.Overcharged A / C system.
Faulty condenser cooling
operation.
Faulty condenser fan
operation.Adjust refrigerant to
specified amount.
Clean condenser.
Inspect and repair
condenser fan.
0.35 ± 0.45(3.5 ± 4.5)
(50 ± 64)
1.96 ± 2.45
(20 ± 25)
(285 ± 355)
High pressure reading on
both low and high pressure
sides.
Low pressure side tubing is
not cold when touched.
Air bubbles are visible
through sight glass.Presence of air in A / C
system. (Improperly
evacuated)Replace receiver / dryer.
Inspect quantity of
compressor oil and
presence of
contaminants in oil.
Evacuate system and
recharge with fresh
refrigerant.
0.45 ± 0.55
(4.5 ± 5.5)
(64 ± 78)
High pressure reading on
both low and high pressure
sides.
Large amount of frost or
dew on the low pressure
side tubing.Faulty expansion valve.
Refrigerant flow is not
regulated properly.Replace expansion
valve.
YH4
GRAND
VITARA
SYSTEM CIRCUIT
A. To heater fuse
B. To rear defogger fuse
C. To ignition / meter fuse
D. To A / C fuse
E. Only LH vehicle1. Blower motor relay
2. Blower motor
3. Blower motor switch
4. A / C switch
5. Deflloster position switch
6. Deflloster / foot position switch7. Dual pressure (refrigerant
pressure) switch
8. A / C thermistor (evaporator
temperature sensor)
9. Compressor relay
10. Compressor11. Condenser fan motor relay
12. Condenser fan motor
13. A / C controller
14. ECM
15. Compressor thermal switch
(only IWATA production vehicle)
TERMINAL ARRANGEMENT OF A / C CONTROLLER
TERMINAL ARRANGEMENT OF ECM FOR G16, J20 ENGINE
TERMINAL ARRANGEMENT OF ECM FOR H25 ENGINE
H25 engine
E61-27
G16, J20
engines
E61-8
H25 engine
E61-28
G16, J20
engines
E61-17
1919
19H25 engine
E61-5
G16, J20
engines
E61-22
AIR CONDITIONING (OPTIONAL) 1B-19
YH4
GRAND
VITARA
For CAMI production vehicle
For IWATA production vehicle
1B-24 AIR CONDITIONING (OPTIONAL)
RECOVERY
NOTE:
When discharging refrigerant out of A / C system, always re-
cover it by using refrigerant recovery and recycling equip-
ment (1). Discharging it into atmosphere would cause ad-
verse effect to environments.
When handling recovery and recycling equipment, be sure
to follow the instruction manual for the equipment.
YH4
GRAND
VITARA
For CAMI production vehicle
For IWATA production vehicle
AIR CONDITIONING (OPTIONAL) 1B-25
EVACUATING
EVACUATING PROCEDURE
CAUTION:
Do not evacuate before recovering refrigerant in system.
NOTE:
Whenever opened (exposed to atmospheric air), air condition-
ing system must be evacuated by using a vacuum pump. The
A / C system should be attached with a manifold gauge set, and
should be evacuated for approx. 15 minutes.
1) Connect high charging hose (1) and low charging hose (2) of
manifold gauge set (3) respectively as follows:
High Charging Hose (1)
High pressure charging valve (4)
on Discharge Hose
Low Charging Hose (2)i
Low pressure charging valve (5)
on Suction Pipe
2) Attach center charging hose (6) of manifold gauge set (3) to vac-
uum pump (7).
3) Operate vacuum pump (7), and then open discharge-side valve
(9) (Hi) of manifold gauge set (3).
If there is no blockage in the system, there will be an indication
on high pressure gauge (10).
When this occurs, open the other-side valve (8) (Lo) of the set.
4) Approx. 10 minutes later, low pressure gauge (11) should show
a vacuum lower than ± 760 mmHg providing no leakage exists.
NOTE:
If the system does not show a vacuum below ± 760 mmHg,
close both valves, stop vacuum pump and watch move-
ment of low pressure gauge.
Increase in the gauge reading suggests existence of leak-
age. In this case, repair the system before continuing its
evacuation.
If the gauge shows a stable reading (suggesting no leak-
age), continue evacuation.
5) Evacuation should be carried out for a total of at least 15 minutes.
6) Continue evacuation until low pressure gauge indicates a vacu-
um less than ± 760 mmHg, and then close both valves (8), (9).
7) Stop vacuum pump (7). Disconnect center charging hose (6) from
pump inlet. Now, the system is ready for charging refrigerant.
CHECKING SYSTEM FOR PRESSURE LEAKS
After completing the evacuation, close manifold gauge high pres-
sure valve (HI) and low-pressure valve (LO) and wait 10 minutes.
Verify that low-pressure gauge reading has not changed.
CAUTION:
If the gauge reading moves closer to ª0º, there is a leak
somewhere. Inspect the tubing connections, make neces-
sary corrections, and evacuate system once again, making
sure that there are no leaks.
YH4
GRAND
VITARA
For CAMI production vehicle
For IWATA production vehicle
1B-26 AIR CONDITIONING (OPTIONAL)
CHARGING
CAUTION:
ALWAYS CHARGE THROUGH LOW PRESSURE-SIDE of A / C system at after the initial charging is per-
formed from the high-pressure side with the engine stopped.
NEVER CHARGE TO HIGH PRESSURE-SIDE of A / C system with engine running.
Do not charge while compressor is hot.
When installing tap valve to refrigerant container to make a hole there through, carefully follow direc-
tions given by manufacturer.
A pressure gauge should always be used before and during charging.
The refrigerant container should be emptied of refrigerant when discarding it.
The refrigerant container should not be heated up to 40C (104F) or over.
Refrigerant container should not be reversed in direction during charging. Reversing in direction
causes liquid refrigerant to enter compressor, causing troubles, such as compression of liquid refrig-
erant and the like.
NOTE:
The air conditioning system contains HFC-134a (R-134a).
Described here is a method to charge the air conditioning system with refrigerant from the refrigerant ser-
vice container.
When charging refrigerant recovered by using the refrigerant and recycling equipment (when recycling
refrigerant), follow the procedure described in the equipment manufacturer's instruction manual.
The initial charging of the A / C system is performed from the high-
pressure side with the engine stopped.
And next, this method must be followed by charging from the low-
pressure side with the engine running.
1) Check to make sure that hoses are routed properly after eva-
cuating the system.
2) Connect Low-side hose (1) and High side hose (2) of the man-
ifold gauge set (3) in position. Thus open refrigerant container
valve (4) to purge the charging line.
3) Open the high-pressure side valve (6) and charge refrigerant to
system.
4) After a while, open the low-pressure side valve (5) and close the
high-pressure side valve (6).
WARNING:
Make sure that high pressure-side valve is closed se-
curely.
5) Start engine and keep engine speed at 1500 r / min. Then, oper-
ate air conditioning.
6) Charge A / C system with refrigerant in vapor state. At this time,
refrigerant container should be held upright.
YH4
GRAND
VITARA
For CAMI production vehicle
For IWATA production vehicle
1B-28 AIR CONDITIONING (OPTIONAL)
8) After the system has been charged with specified amount of re-
frigerant or when low pressure gauge (1) and high pressure
gauge (2) have indicated about 2 and 15 kg / cm
2 respectively,
close low pressure side vale (3) of manifold gauge set (4). If
equipped with sight glass in this time, look into the sight glass (6)
of condenser outlet pipe (5) and check that there are no bubbles
(7) in it, which means that the system is fully charged.
Low pressure gauge when charged with specified amount:
About 200 ± 300 kPa (2 ± 3 kg / cm
2, 29 ± 43 psi)
(At A / C inlet temperature 30 ± 35C, 86 ± 95F)
High pressure gauge when charged with specified amount:
About 1370 ± 1670 kPa (14 ± 17 kg / cm
2, 200 ± 244 psi)
(At A / C inlet temperature 30 ± 35C, 86 ± 95F)
YH4
GRAND
VITARA
1. Electric leak detector
AIR CONDITIONING (OPTIONAL) 1B-29
REMOVING MANIFOLD GAUGE SET
When A / C system has been charged with a specified amount of re-
frigerant, remove manifold gauge set as follows:
1) Close low pressure-side valve of manifold gauge set, (The high
pressure-side valve is closed continuously during the process
of charging.).
2) Close refrigerant container valve.
3) Stop engine.
4) Using shop rag, remove charging hoses from service valves.
This operation must be performed rapidly.
WARNING:
High pressure-side is naturally under high pressure.
So, care must be used to protect your eyes and skin.
5) Put caps on service valves.
LEAK-TESTING REFRIGERANT SYSTEM
Whenever a refrigerant leak is suspected in the system or any ser-
vice operation has been performed which may result in disturbing
lines or connections, it is advisable to test for leaks.
Common sense should be used in performing any refrigerant leak
test, since the need and extent of any such test will, in general, de-
pend upon the nature of a complaint and the type of a service per-
formed on the system.
LIQUID LEAK DETECTORS
There are a number of fittings and places throughout the air condi-
tioning system where a liquid leak detector solution may be used
to pinpoint refrigerant leaks.
By merely applying the solution to the area in question with a swab,
bubbles will form within seconds if there is a leak.
For confined areas, such as sections of the evaporator and con-
denser, an electronic (gas) leak detector is more practical for deter-
mining leaks.
WARNING:
To prevent explosions or fires, make sure that there are no
flammables in the vicinity.
When exposed to fire, the refrigerant turns into a poison-
ous gas (phosgene). Do not inhale this gas.