MANULLI calibrated seal (3).
Direction of fitting of the seal (3).
Before fitting the seal, amply lubricate the seal with air conditioningcompressor oil
(SP10). The condenser
(5)has a cylinder (6)incorporating the function of aircon
fluid reservoir and with integral filtering cartridge.The inlet
(7)and the outlet (8)of the condenser (5)are equipped with
new seals (3) (MANULLI).
SPECIAL FEATURES: AIR CONDITIONING SYSTEM (R 134.a)
Seals (MANULLI seal)
Condenser (MANULLI seal)
C5HP18VDC5HP18XD
C2 C3 XSARA PICASSO
Downloaded from www.Manualslib.com manuals search engine 496
SPECIAL FEATURES: AIR CONDITIONING SYSTEM (R 134.a)
Compressor lubricant
ESSENTIAL: The compressor lubricant is extremely hygroscopic; always use FRESH oil.
Checking the compressor oil level
There are three specific cases:
1/
Repairs to a system without leaks.2/Slow leak.3/Fast leak.
1/ Repairing a system without leaks.
a)Using draining/recovery equipment not fitted with an oil decanter.
Drain the system as slowly as possible via the LOW PRESSUREvalve, so as not to lose any oil.
No more oil should be added when filling the system with
R 134.a fluid.
b) Using draining/filling equipment fitted with an oil decanter. Drain the R 134.afluid from the system in accordance with the instructions in the equipment handbook.
Measure the amount of oil recovered.
Add the same amount of
NEWoil when filling the system with R 134.afluid.
c) Replacing a compressor. Remove the old compressor, drain it and measure the oil quantity.
Drain the new compressor (supplied full), so that the same amount of NEWoil is left in the compressor as was in the old compressor.
No more oil should be added when filling the system with R 134.afluid.
AIRCONAIRCON