ADJUSTMENT SERVICING PRECAUTIONS
Care must be taken when handling refrigeration
system components. Units must not be lifted by their
hoses, pipes or capillary lines. Hoses and lines must
not be subjected to any twist or stress. Ensure that
hoses are positioned in their correct run before fully
tightening the couplings, and ensure that all clips and
supports are used. Torque wrenches of the correct
type must be used when tightening refrigerant
connections to the stated value. An additional wrench
must be used to hold the union to prevent twisting of
the pipe.
Before connecting any hose or pipe ensure that
refrigerant oil is applied to the seat of the new '0' ring
but not to the threads.
Check the oil trap for the amount of oil lost.
All protective plugs on components must be left in
place until immediately prior to connection.
The receiver/drier contains desiccant which absorbs
moisture. It must be positively sealed at all times.
CAUTION: Whenever the refrigerant
system is opened, the receiver/drier must
be renewed immediately before evacuating
and recharging the system.
Use alcohol and a clean cloth to clean dirty
connections.
Ensure that all new parts fitted are marked for use
withR134a.
Refrigerant oil
Use the approved refrigerant lubricating oil:
Nippon Denso ND-OIL 8
Unipart R134a ND-OIL8
CAUTION: Do not use any other type of
refrigerant oil.
Refrigerant oil easily absorbs water and must not be
stored for long periods. Do not pour unused oil back
into the container.
When renewing system components, add the
following quantities of refrigerant oil:
Condenser 40ml..........................................................
Evaporator 80ml..........................................................
Pipe or hose 20ml........................................................
Receiver/drier 20ml......................................................
Total of refrigerant oil in system = 180ml = 6.3 Fl
ozA new compressor is sealed and pressurised with
Nitrogen gas, slowly release the sealing cap, gas
pressure should be heard to release as the seal is
broken.
NOTE: A new compressor should always
have its sealing caps in place and must
not be removed until immediately prior to
fitting
Fitting a new compressor
A new compressor is supplied with an oil fill (X) of:
180ml
A calculated quantity of oil must be drained from a
new compressor before fitting.
To calculate the quantity of oil to be drained:
1.Remove sealing plugs from the OLD compressor
2.Invert compressor and gravity drain oil into
measuring cylinder. Rotating the compressor
clutch plate will assist complete draining.
3.Note the quantity of oil drained (Y).
4.Calculate the quantity (Q) of oil to be drained
from the NEW compressor using the following
formula:
X - (Y + 20ml) = Q
Rapid refrigerant discharge
When the air conditioning system is involved in
accident damage and the circuit is punctured, the
refrigerant is discharged rapidly. The rapid discharged
of refrigerant will also result in the loss of most of the
oil from the system. The compressor must be
removed and all the remaining oil in the compressor
drained and refilled as follows:
1.Gravity drain all the oil, assist by rotating the
clutch plate (not the pulley).
2.Refill the compressor with the following amount
of new refrigerant oil:
130ml
3.Plug the inlet and outlet ports.
Page 766 of 873

AIR CONDITIONING
1
REPAIR PRECAUTIONS IN HANDLING REFRIGERANT
LINES
WARNING: Wear eye and hand protection
when disconnecting components
containing refrigerant. Plug all exposed
connections immediately.
1.When disconnecting any hose or pipe
connection the system must be discharged of all
pressure. Proceed cautiously, regardless of
gauge readings. Open connections slowly,
keeping hands and face well clear, so that no
injury occurs if there is liquid in the line. If
pressure is noticed, allow it to bleed off slowly.
2.Lines, flexible end connections and components
must be capped immediately they are opened to
prevent the entrance of moisture and dirt.
3.Any dirt or grease on fittings must be wiped off
with a clean alcohol dampened cloth. Do not use
chlorinated solvents such as trichloroethylene. If
dirt, grease or moisture cannot be removed from
inside the hoses, they must be replaced with
new hoses.
4.All replacement components and flexible end
connections must be sealed, and only opened
immediately prior to making the connection.
5.Ensure the components are at room temperature
before uncapping, to prevent condensation of
moisture from the air that enters.
6.Components must not remain uncapped for
longer than fifteen minutes. In the event of delay,
the caps must be fitted.
7.Receiver/driers must never be left uncapped as
they contain Silica Gel crystals which will absorb
moisture from the atmosphere. A receiver/ drier
left uncapped must not be used, fit a new unit.
8.The compressor shaft must not be rotated until
the system is entirely assembled and contains a
charge of refrigerant.
9.A new compressor contains an initial charge of
of refrigerant oil. The compressor also contains a
holding charge of gas when received which
should be retained by leaving the seals in place
until the pipes are re-connected.10.The receiver/drier should be the last component
connected to the system to ensure optimum
dehydration and maximum moisture protection of
the system.
11.All precautions must be taken to prevent
damage to fittings and connections. Slight
damage could cause a leak with the high
pressures used in the system.
12.Always use two wrenches of the correct size,
one on each fitting when releasing and
tightening refrigeration unions.
13.Joints and 'O' rings should be coated with
refrigeration oil to aid correct seating. Fittings
which are not lubricated with refrigerant oil are
almost certain to leak.
14.All lines must be free of kinks. The efficiency of
the system is reduced by a single kink or
restriction.
15.Flexible hoses should not be bent to a radius
less than 90mm.
16.Flexible hoses should not be within 100mm of
the exhaust manifold.
17.Completed assemblies must be checked for
refrigeration lines touching metal panels. Any
direct contact of lines and panels transmits noise
and must be eliminated.
Page 822 of 873
86ELECTRICAL
2
REPAIR FUSE BOX - ENGINE COMPARTMENT
The fusebox is located on the right side of the engine compartment. The circuits protected and their locations are
shown on the inside of the fusebox cover. To change a main circuit fuse prise off protective cover A and remove
retaining screws.
Fuses
1. Heated rear window
2. Sidelights
3. Air conditioning
4. Hazard warning lights, horn
5. ABS valve
6. Fuel pump
7. Fuel injectors
A Main circuit fuses
8. ABS pump
9. Ignition circuits
10. Lighting
11. Window lift, central door locking, rear blower
12. Heater, air conditioning
13. Generator
Page 854 of 873
86ELECTRICAL
34
REPAIR PRINTED CIRCUIT AND WARNING LIGHTS
1. Panel illumination bulbs
2. Transmission oil temperature warning lamp bulb
3. Hazard warning lamp bulb
4. Check engine warning lamp bulb
5. Handbrake/brake fluid warning lamp bulb
6. ABS warning lamp bulb
7. Headlamp main beam warning lamp bulb
8. Trailer direction warning lamp bulb9. Direction indicator warning lamp bulb
10. Air suspension warning lamp bulb
11. Ignition/no charge warning lamp bulb
12. Seat belt warning lamp bulb
13. Not used
14. Traction control warning lamp bulb
15. Diesel heater plug warning lamp bulb (if fitted)
16. Main printed circuit