
CHAPTER 11
THE ELECTRICAL EQUIPMENT
11:1 Description
11:2 Battery
11:3 The generator
11:4 The starter
11:5 The control box
1 1 : 6 Fuses
1 1 : 7 Flasher unit
11:1 Description
All models covered by this manual have 12 volts
electrical systems in which the negative battery terminal
is earthed. There are three units in the regulator box to
control the charging circuit; a cut-out, a current regulator
and a voltage regulator. These are adjustable but it must
be stressed  that accurate moving coil meters are required
when checking or altering the settings.  Cheap and
unreliable instruments will make accurate adjustments
impossible.
There are wiring diagrams in Technical Data at the end
of this manual to enable those with electrical experience
to trace and  correct wiring faults.
For  t h e   U.K.  Market the headlamps are of the double
filament dipping renewable bulb type with adjustments
for individual beam settings.
The battery is located in the front compartment
forward of the petrol tank and the fuses to the rear  o f  the
petrol tank.
Detailed instructions for servicing the electrical equip-
ment will be found in this chapter, but it must be pointed
out that it is not sensible to try to repair that which is
seriously defective, electrically or mechanically. Such
equipment should  be replaced by new units which can
be obtained on an exchange basis.
F500111
11 :8  Windscreen wipers
1 1 : 9 The lighting system
11:10 Panel and warning lights
11:11 The  horn
11:12 Lighting and flasher switch
1 1 : 1 3 Fault diagnosis
11.2 The battery
This of the 12-volt lead/acid type and has to meet
heavy demands for current particularly in the winter. To
maintain the performance of the battery at its maximum
it is essential to carry out the following operations.
Keep the top of the  battery and surrounding parts dry
and clean, as dampness can  cause leakage between the
securing clamps and the battery terminals. Clean off any
corrosion from the metal parts of the battery mounting
with diluted ammonia and  paint them with an anti-
sulphuric paint. If the terminal posts are corroded,
remove the cables and  clean w i t h diluted ammonia.
Smear the  posts w i t h petroleum jelly before remaking the
connections and fit the terminals securely. High electrical
resistance due to corrosion at the terminal posts is often
responsible for lack of sufficient current to operate the
starter motor.
Ensure t h a t the filler plugs are in good condition and
show no signs of cracks. This may cause leakage of
electrolyte and consequent corrosion. Test the condition
of the cells after topping-up the electrolyte level with
distilled water to just above the tops of the separators as
shown in FIG 11 :2 . Never add neat acid. If it is
necessary to make a new electrolyte due to  loss  by
spillage add  sulphuric acid to the 
distilled water.
It is highly dangerous to  add water to acid. 

Checking cut-out:
1 Closing voltage:
This test should be carried out at a temperature of
25°±10°C and the regulator should be connected to a
generator test bed as shown in FIG 11:7. The unit should
be operated  under no  load conditions for  between 15 -
18 minutes with the cover installed and w i t h a voltage of
between 16.5 volts for an  initial  operating temperature of
15-20°C or 15 volts for an initial operating temperature
of 20-35°C.  This will enable thermal stabilization of the
unit to be obtained so that the temperature of both the
cut-out shunt windings and the bymetallic springs
increase due to the heat developed by the windings and
reaches the normal operating setting.
Once thermal stabilization has been obtained the
generator should be restarted  and the speed gradually
increased so that immediately the test lamp starts to
glow the voltmeter  reading may be taken. This will be
the value of the cut-out contact closing voltage.
2 Reverse current:
This check should be carried out at a temperature range
of between 25°±10°C and  it  is recommended that it is
performed as soon as possible after the closing voltage
test so that the thermal stabilization remains unaltered.
Connect the regulator as shown  in FIG 11:8 and
gradually speed  up the generator to 4500 rev/min for
approximately 5 minutes. Ensure that the voltmeter reads
at least 14.5 volts and then gradually reduce the generator
speed carefully watching the movement of the ammeter
needle which should at first indicate a charging current
and then gradually move to zero and then to the other side
of the scale to  indicate reverse current value.  If the
generator speed is reduced further the reverse current
reading will increase to a  given value and then suddenly
fall to zero which will indicate that the cut-out contact
has opened. This limit indicates the  maximum reverse
current value which should not, under any circumstances,
exceed 16 amps.
During this test, to obtain the maximum reverse
current possible the reduction in generator speed must
not take more than  10 seconds otherwise the battery
voltage will drop excessively.
Checking voltage regulator:
This test should  be carried out w i t h the regulator under
half load and at a temperature of 50°± 3°C. Connect the
regulator as shown  in FIG 11:9 and operate the  regulator
for approximately 30 minutes by supplying a current half
that of regulated  current which is 1 6 ±5 amp. Once the
regulator has been brought to  the required temperature
stop the generator and start it again, gradually increasing
the speed to a maximum of 4500 rev/min. Adjust the
rheostat for a generator output corresponding to half load
current of 8 ± 2 amps. When this generator output has
been set the voltage should be 14.2± .3 volts.
Checking current regulator:
Leave the regulator connected as shown in
 FIG 11 :10
and this test must be carried out immediately after testing
the half load regulated voltage of the voltage regulator
when connected to a battery. Check that the  ammeter
fitted will accommodate a 40 amp deflection: if not a
F500117
FIG 11 :9  Wiring diagram for checking the current and
voltage regulators
Key to  Fig  11:9  GR Regulator GN 1.1 2.1 6  G  Generator
FIAT D 90.12.16.3 V Voltmeter, 20 V scale (0.5% accuracy)
A Ammeter, 20 A scale (to check voltage regulator)  and 40 A
scale (to check current regulator)
B Battery, 50 Ah, fully chargedR Rheostat, 25 A. 3
FIG 11 :10  Wiring diagram for setting the cut-out relay
Key to  Fig 11 :10 B 2 V battery B 20 V batteryA Ammeter, 20 A scale ( 1 % accuracy) V Voltmeter, 20 V
scale (0.5% accuracy), directly connected to terminals 31—51
P Potentiometer for voltage adjustment, having such a capacity
that the current draw  of the cut-out shunt winding does not
cause sensible variations in the voltage readings (voltmeter
under no load) S Test lamp, with 2 V, 3 W bulb, to signal
opening and closing of contacts R Rheostat, 4 12
 AR Voltage drop resistor, suitable to allow turning on of A withT open and cut-out contacts open
Setting of instruments before inserting the unit: P At
minimum (voltmeter reads zero) T Open R All inserted
(max. resistance) T Open
FIG 11:11 Wiring diagram for setting the voltage and
current regulators
Key to Fig 11 :11  GR Regulator assembly GN  1.12.16
G Generator D 90.12.16.3 V Voltmeter, 20 V scale (0.5%
accuracy) A Ammeter, 20 Amp. scale (for voltage regulator),
or 40 Amp. scale (for current regulator) R Rheostat, 25
Amps., 3 Ohms B 50 Amp/h battery, fully charged I Switch 

Checking cut-out:
1 Closing voltage:
This test should be carried out at a temperature of
25°±10°C and the regulator should be connected to a
generator test bed as shown in FIG 11:7. The unit should
be operated  under no  load conditions for  between 15 -
18 minutes with the cover installed and w i t h a voltage of
between 16.5 volts for an  initial  operating temperature of
15-20°C or 15 volts for an initial operating temperature
of 20-35°C.  This will enable thermal stabilization of the
unit to be obtained so that the temperature of both the
cut-out shunt windings and the bymetallic springs
increase due to the heat developed by the windings and
reaches the normal operating setting.
Once thermal stabilization has been obtained the
generator should be restarted  and the speed gradually
increased so that immediately the test lamp starts to
glow the voltmeter  reading may be taken. This will be
the value of the cut-out contact closing voltage.
2 Reverse current:
This check should be carried out at a temperature range
of between 25°±10°C and  it  is recommended that it is
performed as soon as possible after the closing voltage
test so that the thermal stabilization remains unaltered.
Connect the regulator as shown  in FIG 11:8 and
gradually speed  up the generator to 4500 rev/min for
approximately 5 minutes. Ensure that the voltmeter reads
at least 14.5 volts and then gradually reduce the generator
speed carefully watching the movement of the ammeter
needle which should at first indicate a charging current
and then gradually move to zero and then to the other side
of the scale to  indicate reverse current value.  If the
generator speed is reduced further the reverse current
reading will increase to a  given value and then suddenly
fall to zero which will indicate that the cut-out contact
has opened. This limit indicates the  maximum reverse
current value which should not, under any circumstances,
exceed 16 amps.
During this test, to obtain the maximum reverse
current possible the reduction in generator speed must
not take more than  10 seconds otherwise the battery
voltage will drop excessively.
Checking voltage regulator:
This test should  be carried out w i t h the regulator under
half load and at a temperature of 50°± 3°C. Connect the
regulator as shown  in FIG 11:9 and operate the  regulator
for approximately 30 minutes by supplying a current half
that of regulated  current which is 1 6 ±5 amp. Once the
regulator has been brought to  the required temperature
stop the generator and start it again, gradually increasing
the speed to a maximum of 4500 rev/min. Adjust the
rheostat for a generator output corresponding to half load
current of 8 ± 2 amps. When this generator output has
been set the voltage should be 14.2± .3 volts.
Checking current regulator:
Leave the regulator connected as shown in
 FIG 11 :10
and this test must be carried out immediately after testing
the half load regulated voltage of the voltage regulator
when connected to a battery. Check that the  ammeter
fitted will accommodate a 40 amp deflection: if not a
F500117
FIG 11 :9  Wiring diagram for checking the current and
voltage regulators
Key to  Fig  11:9  GR Regulator GN 1.1 2.1 6  G  Generator
FIAT D 90.12.16.3 V Voltmeter, 20 V scale (0.5% accuracy)
A Ammeter, 20 A scale (to check voltage regulator)  and 40 A
scale (to check current regulator)
B Battery, 50 Ah, fully chargedR Rheostat, 25 A. 3
FIG 11 :10  Wiring diagram for setting the cut-out relay
Key to  Fig 11 :10 B 2 V battery B 20 V batteryA Ammeter, 20 A scale ( 1 % accuracy) V Voltmeter, 20 V
scale (0.5% accuracy), directly connected to terminals 31—51
P Potentiometer for voltage adjustment, having such a capacity
that the current draw  of the cut-out shunt winding does not
cause sensible variations in the voltage readings (voltmeter
under no load) S Test lamp, with 2 V, 3 W bulb, to signal
opening and closing of contacts R Rheostat, 4 12
 AR Voltage drop resistor, suitable to allow turning on of A withT open and cut-out contacts open
Setting of instruments before inserting the unit: P At
minimum (voltmeter reads zero) T Open R All inserted
(max. resistance) T Open
FIG 11:11 Wiring diagram for setting the voltage and
current regulators
Key to Fig 11 :11  GR Regulator assembly GN  1.12.16
G Generator D 90.12.16.3 V Voltmeter, 20 V scale (0.5%
accuracy) A Ammeter, 20 Amp. scale (for voltage regulator),
or 40 Amp. scale (for current regulator) R Rheostat, 25
Amps., 3 Ohms B 50 Amp/h battery, fully charged I Switch 

FIG 11:12 Wiring diagram for setting the cutout relay
Key to  Fig  11  :12  B  2 V battery B 20 V battery
A Ammeter, 15 A scale ( 1 % accuracy) V Voltmeter, 20 V
scale (0.5% accuracy), directly connected to terminals 31-51
P Potentiometer for voltage adjustment, having such a capacity
that the current draw of the cutout shunt winding does not cause
sensible variations in  the voltage readings (voltmeter under no
load) S Test lamp, with 2 V, 3 W bulb, to signal opening
and closing of contacts R Rheostat, 4  , 1 2 A R Voltagedrop rheostat, suitable to allow turning on of S with T open and
cutout contacts open
Setting of instruments before inserting the unit: P At
minimum (Voltmeter reads zero) T Open R All inserted
(max. resistance) T Open
1
2
3
4
5
6
FIG 11:13 Location of electrical system fuses
Key to  Fig  11 :13 1 Fuse N o . 30.2 2 Fuse N o . 30.3
3 Fuse N o . 56.b1 4 Fuse N o . 56.b2 5 Fuse N o . 15.54
6 Fuse N o . 30
meter w i t h  a fuller scale deflection of 40 amp must be
substituted. Adjust the rheostat to  give maximum
resistance and operate the regulator for approximately
30 minutes with  regulator controlled current and  13 volt
supply. The resistor R of the rheostat should be adjusted
until the current is steady whilst the voltage drops.  This
will indicate that the  unit  has reached normal operating
temperature. Stop the generator, restart it and speed  up
gradually to 4500  rev/min. Check that the  regulated
current value corresponds to the specified value of
1 6± .5  amps.  By continually reducing the resistance the
current should remain constant. The voltage however
should decrease to as l o w as 12 volts.
118
Cut-out relay adjustment:
Ascertain the type of regulator fitted and then wire to
the test unit as shown  in FIG 11:10 or FIG 11 :12.
Before the unit is assembled to the test  bed the instru-
ments should be set as follows:
P - at minimum so that voltmeter reads zero.
T — open.
R - all inserted giving maximum resistance.
T - open.
1 Contact closing voltage:
This test should be carried out at an  ambient tempera-
ture of 25°±10°C.  Close the switch T and stabilize the
regulator thermally by feeding current into it for  approxi-
mately 15 to 18 minutes at 16.5 volts which is obtained
by adjusting  P for initial regulator operating temperatures
of between  15°-20°C or at 15 volts for initial  operating
temperatures of 20°-35°C. Once the stabilizing of the
regulator has been completed  bring the voltage to 12 6±
.2 volts by adjusting P. Adjust the load on the setting
spring by bending the relevant arm  until the pilot light S
is extinguished. Reset  P  to  m inimum and again increase
the voltage by P and check that the pilot lamp is extin-
guished at the specified voltage.
2 Reverse current:
This test must be carried out at a temperature of
25°± 10°C and  it is recommended that it is carried out as
soon as possible after the closing voltage test so as to
maintain minimum regulator thermal stability. With the
switch T closed bring the voltage to 14.5 volts by
operating  P. The contacts of the cut-out should be closed
and the pilot lamp S off.  Close T  and increase the reverse
current by means of the rheostat R  and check that the
pilot lamp S glows as the contacts part. The opening may
also be unsteady which will  be indicated  by a slight
buzz from the unit. Check the value of the ammeter of the
reverse current causing the opening of the contacts and
this should  not exceed 16 amps. If the reading is unstable
or S  lights  up at the recommended limit reset the reverse
current to the  minimum value and repeat the test once
more. Finally open the switches T  and T  and again
adjust rheostat R and  P to the minimum settings.
Voltage regulator adjustment:
This test should  be carried  out at a temperature of
5 0 ° ±3 ° C . Connect the unit as shown in FIG 11 :11 and
load the voltage regulator adjusting springs by bending
the relevant arm. With the unit at the required test
temperature close 1 start the generator and stabilize
the regulator thermally by feeding a current for 30
minutes at 15 volts, which is obtained by adjusting the
generator speed. The generator should then  be stopped,
I opened and the generator restarted and gradually
speeded  up to 4500 rev/min. The voltage regulator
spring load adjustment should  be set by suitably bending
the relevant adjusting arm and by rheostat R so as to have
a voltage of 14.2±.3 volts and  a half load current of
8 ± 2 amps.  Finally check the steadiness and accuracy
of the voltage regulator setting by stopping the generator
and restarting after approximately 2 minutes and gradually
speeding up to 4500 rev/min. 

FIG 12:1 Detail of right door (early type). Upper arrow
points to  vent wing lock  handle. Lower arrow points to
window regulator handle
FIG  1 2 : 2   Sedan  right  side  door  (later type). Front-hinged.
Door  latch is of the triple acting type. Later  (pull-out) type
interior  lock  handles  have  an  escutcheon  which is levered
out  by  means  of  t w o  screwdrivers  to  expose  the  handle
pivot  pin  and  spring
Cleaning imitation leather:
To keep the imitation leather clean wash in luke warm
water and a  neutral soap applied with a soft cloth. Wipe
clean with a clean moistened cloth with no trace of soap
and  finally rub with  a  clean dry cloth  until the original
lustre is restored.
128
Chrome plated parts:
To ensure long life from the chrome plated parts these
should be periodically washed using a cloth dampened
with petrol and dried with a soft cloth.  Rub with a cloth
moistened in clean oil especially around the edges of the
components and finally rub using a clean dry cloth until
all traces of oil have been apparently removed.
Glass panels:
The glass panels must be cleaned w i t h a chamois
leather or rag. Take care that  no abrasive material  is
allowed to be rubbed onto the glass otherwise it will be
scratched.
12:3 Door trim and accessories
The rear-hinged doors have welded upper and lower
hinge halves being joined  by a fulcrum pin to the other
half of the  hinge which is welded onto the body.  Upon
reassembly of a  hinge the fulcrum pins must be fitted with
the ball  head uppermost. With front-hinged doors the
hinge is bolted to the body pillar.
Check strap (earlier models):
To limit the door opening,  a rubber check strap  is fixed
by four self-tapping screws of which two are located on
the door and t w o on the body. When a check strap is being
fitted the following points should  be noted:
1 Always use sealing compound on the check strap
mounting holes to ensure a moisture t i g h t j o i n t .
2 Insert the screws in the plates and  in the strap.
3 Always place a washer on each screw between the
body and the check strap, and also the door and check
strap. Tighten the screws fully.
Weather strip:
A one-piece moulded weather strip  is fitted to the door
aperture and fixed by a special adhesive. Should the
weather strip become detached or a new one requiring to
be fitted proceed as follows:
1 Remove the old weather strip as necessary and thor-
oughly clean the door opening flange with petrol,
remove any rust spots and touch in the paint work.
2 Clean the new weather strips of their preservative or
the original from road dirt using petrol and thoroughly
wipe 
clean.
3  Apply a  coat of adhesive using a brush to the side to  be
attached to the body. Allow to dry for the recom-
mended period of time and position the weather strip
on the door opening flange ensuring that it is not
distorted. The joint should be on the bottom side of
the rear end of the door opening. Apply a  heavy
pressure on the weather strip starting from the centre
and working towards the ends.
Two rubber lining strips are located on the door flange
and these should be attached using the same procedure
detailed above.
Ensure that the bonding of the rubber weather strips
to both the door opening flange and  the door  panel  is
thoroughly dry before the door is closed, otherwise this
could be the cause of subsequent water ingress.